R410A Pressure-Temperature Chart

For superheat and subcooling calculations in HVAC systems

About This Chart

This pressure-temperature chart shows the relationship between the pressure and saturation temperature for R410A refrigerant. Use this chart to calculate superheat and subcooling when troubleshooting or commissioning HVAC systems.

Superheat = Actual temperature - Saturation temperature (at suction pressure)

Subcooling = Saturation temperature (at liquid pressure) - Actual temperature

Lower Temperature Range Higher Temperature Range
Temperature
°F
Temperature
°C
Pressure
PSIG
Pressure
kPa
Temperature
°F
Temperature
°C
Pressure
PSIG
Pressure
kPa
-40 -40.0 14.6 100.7 60 15.6 192.9 1330.0
-35 -37.2 18.3 126.2 65 18.3 214.0 1475.5
-30 -34.4 22.5 155.1 70 21.1 236.4 1629.9
-25 -31.7 27.2 187.5 75 23.9 260.2 1793.9
-20 -28.9 32.4 223.4 80 26.7 285.4 1967.8
-15 -26.1 38.2 263.4 85 29.4 312.1 2152.5
-10 -23.3 44.6 307.5 90 32.2 340.3 2346.3
-5 -20.6 51.6 355.8 95 35.0 370.0 2551.1
0 -17.8 59.3 408.9 100 37.8 401.3 2766.9
5 -15.0 67.7 466.8 105 40.6 434.1 2993.1
10 -12.2 76.9 530.2 110 43.3 468.8 3231.7
15 -9.4 86.8 598.5 115 46.1 505.3 3483.3
20 -6.7 97.5 672.3 120 48.9 543.6 3747.5
25 -3.9 109.1 751.6 125 51.7 583.8 4025.3
30 -1.1 121.6 838.4 130 54.4 626.0 4316.9
35 1.7 135.1 931.5 135 57.2 670.1 4620.9
40 4.4 149.6 1031.5 140 60.0 716.4 4939.1
45 7.2 165.2 1139.1 145 62.8 764.9 5273.3
50 10.0 178.3 1229.4 150 65.6 815.7 5623.7
55 12.8 193.1 1331.4