Refrigerant Pipe Sizing Guide

For proper refrigerant line sizing in HVAC and refrigeration systems

About This Guide

Proper refrigerant line sizing is critical for system performance, efficiency, and longevity. This guide provides sizing recommendations for common refrigerants and system capacities.

Key considerations for refrigerant line sizing:

General Guidelines

R410A Pipe Sizing Chart

The following tables provide recommended pipe sizes for R410A refrigerant systems. All sizes are in inches OD (outside diameter).

Suction Line Sizing - R410A

System Capacity
(Tons)
System Capacity
(BTU/h)
Line Size
Up to 25 ft
Line Size
25-50 ft
Line Size
50-100 ft
Line Size
Over 100 ft
Max Recommended
Length (ft)
1.0 12,000 5/8" 5/8" 3/4" 3/4" 150
1.5 18,000 5/8" 3/4" 3/4" 7/8" 150
2.0 24,000 3/4" 3/4" 7/8" 7/8" 175
2.5 30,000 3/4" 7/8" 7/8" 1-1/8" 175
3.0 36,000 3/4" 7/8" 1-1/8" 1-1/8" 175
3.5 42,000 7/8" 1-1/8" 1-1/8" 1-1/8" 200
4.0 48,000 7/8" 1-1/8" 1-1/8" 1-3/8" 200
5.0 60,000 1-1/8" 1-1/8" 1-3/8" 1-3/8" 200
7.5 90,000 1-3/8" 1-3/8" 1-5/8" 1-5/8" 225
10.0 120,000 1-5/8" 1-5/8" 1-5/8" 2-1/8" 225

Liquid Line Sizing - R410A

System Capacity
(Tons)
System Capacity
(BTU/h)
Line Size
Up to 25 ft
Line Size
25-50 ft
Line Size
50-100 ft
Line Size
Over 100 ft
Max Recommended
Length (ft)
1.0 12,000 1/4" 1/4" 3/8" 3/8" 150
1.5 18,000 1/4" 1/4" 3/8" 3/8" 150
2.0 24,000 3/8" 3/8" 3/8" 1/2" 175
2.5 30,000 3/8" 3/8" 3/8" 1/2" 175
3.0 36,000 3/8" 3/8" 1/2" 1/2" 175
3.5 42,000 3/8" 3/8" 1/2" 1/2" 200
4.0 48,000 3/8" 1/2" 1/2" 5/8" 200
5.0 60,000 1/2" 1/2" 5/8" 5/8" 200
7.5 90,000 1/2" 5/8" 5/8" 3/4" 225
10.0 120,000 5/8" 5/8" 3/4" 3/4" 225

R407C Pipe Sizing Chart

The following tables provide recommended pipe sizes for R407C refrigerant systems. All sizes are in inches OD (outside diameter).

Suction Line Sizing - R407C

System Capacity
(Tons)
System Capacity
(BTU/h)
Line Size
Up to 25 ft
Line Size
25-50 ft
Line Size
50-100 ft
Line Size
Over 100 ft
Max Recommended
Length (ft)
1.0 12,000 5/8" 3/4" 3/4" 7/8" 150
1.5 18,000 3/4" 3/4" 7/8" 7/8" 150
2.0 24,000 3/4" 7/8" 7/8" 1-1/8" 175
2.5 30,000 7/8" 7/8" 1-1/8" 1-1/8" 175
3.0 36,000 7/8" 1-1/8" 1-1/8" 1-3/8" 175
3.5 42,000 1-1/8" 1-1/8" 1-3/8" 1-3/8" 200
4.0 48,000 1-1/8" 1-1/8" 1-3/8" 1-3/8" 200
5.0 60,000 1-1/8" 1-3/8" 1-3/8" 1-5/8" 200
7.5 90,000 1-3/8" 1-5/8" 1-5/8" 2-1/8" 225
10.0 120,000 1-5/8" 1-5/8" 2-1/8" 2-1/8" 225

Equivalent Length for Fittings

When calculating total equivalent length, add the following values for each fitting in the system.

Fitting Equivalent Length (in feet)

Fitting Type 3/8" 1/2" 5/8" 3/4" 7/8" 1-1/8" 1-3/8" 1-5/8" 2-1/8"
90° Elbow 1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0 7.0
45° Elbow 0.5 0.8 1.0 1.3 1.5 2.0 2.5 3.0 3.5
Tee (Branch) 3.0 4.5 5.5 6.5 7.5 9.0 11.0 13.0 17.0
Tee (Run) 0.5 0.8 1.0 1.5 1.5 2.0 2.5 3.0 4.0
Check Valve 3.0 4.0 5.0 6.0 7.0 10.0 12.0 15.0 20.0
Globe Valve 15.0 20.0 25.0 30.0 35.0 45.0 55.0 65.0 85.0
Ball Valve 0.5 1.0 1.5 2.0 2.5 3.0 4.0 5.0 6.0

Installation Guidelines

Vertical Risers

For suction line risers (refrigerant flowing upward to the compressor):

  • Install oil traps at the bottom of each vertical riser
  • Install additional traps for every 20 feet of vertical rise
  • Properly size risers to maintain adequate refrigerant velocity for oil return
  • Minimum recommended velocity: 1000 ft/min for proper oil return

Note: In systems with long risers, consider reducing pipe size by one size to maintain proper velocity for oil return. Consult manufacturer specifications.

Long Line Applications

For installations exceeding the maximum recommended lengths:

  • Add additional refrigerant charge for longer line sets
  • Consider adding a suction line accumulator
  • Install a crankcase heater on the compressor
  • Use hard-drawn copper tubing (ACR) for all refrigerant lines
  • Consider line loops for vibration isolation and thermal expansion
  • Consult with the equipment manufacturer for specific long-line application guidelines